High Voltage Digital Insulation Meter 250V 500V IP40 Enclosure Protection
VICTOR 3123 Hight Voltage Insulation Resistance Tester 250V/500V/1000V/2500V IP40 Enclosure Protection 0-99.9GΩ Resistance
The Basic Feature
- 4-range Hight voltage insulation resistance test:
- VICTOR3123:250V,500V,1000V ,2500V
- DC/AC Voltage measurement:
DC:00~±1000V AC:30~600V(50/60Hz)
- Liquid crystal display(Max. 9999 counts),36 sect bar graph to display
- Sample rate:apptox.0.5 ~ 5 times/sec
- Hight voltage insulation resistance test Auto-ranging
- PI(Polarization Index),DAR(Induction absorption ratio)can be measured by the automatic measurement function
- Continuous measurement function
- With Timer measurement function
- Automatic Electric discharge function
- Stepping voltage test,temperature measurement,Leakage current display
- The actual output voltage value and the survey insulation resistance value are displayed at the same time
- Built-in real-time clock, provide the accurate time to the record and the surveying work
- Two kind of convenient of operation data record function:Manual record and Work record,and may convenient inquire about data recording
- Uses the panel calibration technology, without opening the crust can be calibrated
- Available alkaline battery,Ni-Hi battery or power adapter power supply,the battery compartment cover may convenient the battery replacement
- Has the automatic backlight closure function and the automatic power source closure function
- Big screen LCD display,with the white LED backlight
- The meter can communicate with computer by isolation interface USB,and can be operated by computer
- The feature of simple man-machine operation,portable and firm suits the field use
Basic Specification
(Apply within one year after the calibration,23℃±5℃,0~70%RH, Accuracy =±(%reading+LSD))
Insulation Resistance tester
| 3123 |
√ |
√ |
√ |
√ |
|
| 3125 |
|
√ |
√ |
√ |
√ |
|
Rated
voltage
|
250V |
500V |
1000V |
2500V |
5000V |
|
Measuring
Range
|
0.0~99.9MΩ
100~999MΩ
1.00~2.50GΩ
|
0.0~99.9MΩ
100~999MΩ
1.00~5.00GΩ
|
0.0~ 99.9MΩ
100~999MΩ
1.00~9.99GΩ
|
0.0~99.9MΩ
100~999MΩ
1.00~9.99GΩ
10.0~99.9GΩ
|
0.0~99.9MΩ
100~999MΩ
1.00~9.99GΩ
10.0~99.9GΩ
100~1000GΩ
1.00~1.20TΩ
|
|
Open circuit
Voltage
|
DC 250V
+ 20% ,-0%
|
DC 500V
+ 20% ,-0%
|
DC 1000V
+ 20%,-0%
|
DC 2500V
+ 20%,-0%
|
DC 5000V
+20%,-0%
|
|
Rated
Current
|
1mA--1.2mA
(at 0.21MΩ load)
|
1mA--1.2mA
(at 0.5MΩ load)
|
1mA--1.2mA
(at 1MΩ load)
|
1mA--1.2mA
(at 2.5MΩ load)
|
1mA—1.2mA
(at 5MΩ load)
|
|
Short-circuit
Current
|
Approx. 1.3mA |
| Accuracy |
±5%rdg ± 3dgt / ±20%(100GΩ or more) |
Voltage monitor display for insulation resistance range
0~5000V(resolution 1V):±2%rdg±3dgt
Leakage current measurement
| Current Range |
Measuring Range |
Accuracy |
| 5uA |
0.000~5.250uA |
±10%rdg±5dgt |
| 50uA |
5.00~52.50uA |
±2.5%rdg±5dgt |
| 250uA |
50.0~262.5uA |
±2.5%rdg±5dgt |
| 1500uA |
250~1500uA |
±2.5%rdg±5dgt |
Voltage measurement
| |
DC voltage |
AC voltage |
|
Measuring
range
|
0~±1000V |
30 ~600V(50/60Hz) |
| Resolution |
1V |
| Accuracy |
±2%rdg±3dgt |
Temperature measurement
| Measuring range |
Accuracy |
| 0.0~25.0ºC |
±1ºC |
| 25.0~70.0ºC |
±2.ºC |
General
- Operating temperature & humidity range:
- 0ºC ~ 40ºC/Relative humidity 85% or less(no condensation)
- Storage temperature & humidity range:
- -20ºC ~ +60ºC/Relative humidity 90% or less(no condensation)
- Operable altitude:2000m or less(used to indoor)
- Rated Transient Overvoltage
- 6KV(1.2*50us)CATⅠ, CAI Ⅱ, CAT Ⅲ peak measurement
- Insulation resistance & Withstand voltage:
- 1000MΩ or more /DC1000V (Between electrical circuit and enclosure)
- AC8320V(50/60Hz)/5sec. (Between electrical circuit and enclosure)
- shake & impact::Randomicity 2g, 5~500Hz
- 1 meter drops the test
- Calibrating period & Preheat interval:
- In order to guarantee that this meter precision, its calibrating period is one year or other
- Starting preheat interval is 10 minutes or other
Display & Backlight:Sect style LCD double display:63.7×104.7mm
White LED backlight, may setup backlight time 0~3600sec
DC12V:Alkaline battery size C(LR14) × 8pcs
DC12V:Ni-Hi battery size C(R14) × 8pcs
the external DC12V adapter
Auto-power-off:may setup Auto-power-off time 0~60minutes
- Dimensions & Weight:210 × 155 × 95(mm),approx. 1300g(barring battery)
- Accessories:A set of test leads Alkaline size C battery (LR14) × 8pcs
- Instruction manual
- Hard Case
- 12V adapter for recorder